S
SoSimple.tools
Vanlife & Off-Grid Electrical

12 V Wire Size & Voltage Drop Calculator

Size DC wiring for campervans, boats and off-grid solar systems. Calculate voltage drop, recommended fuse sizes and wire gauges in mm² and AWG

Runs in your browser: what you enter stays on your device
1

Enter your system voltage, appliance load (Watts or Amps), and one-way cable run length.

2

Pick your max allowed voltage drop, routing environment, and conductor metal type.

3

Get the recommended wire gauge, fuse size, and voltage drop, checked against both voltage-drop and thermal limits.

Circuit & System Parameters

W
Electrical Dimensioning
Recommended Wire Gauge
10 mm² (≈ 6 AWG)
Within this tool's thermal & voltage drop limits
Operating Current
25.0 A
Fuse: 35A - 40A
Actual Voltage Drop
2.92% (0.35 V)
Loss: 8.8 W
Voltage Drop Threshold Utilization 97%

Design stays within this tool's voltage-drop and thermal limits, with low heat loss and some ampacity headroom

Share this tool
Estimate only The results are estimates based on the values you enter and standard formulas. Real conditions, materials, local building and electrical codes, and manufacturer instructions can change what is right for your project. SoSimple.tools does not provide engineering, electrical or construction advice. Check the numbers against the manufacturer's data and your local rules, and ask a qualified professional before building, wiring or buying materials, especially where safety is involved.

How to use this tool

  1. Choose Meters or Feet, the system voltage (12, 24 or 48 V DC) and enter the load in Watts or Amps.
  2. Enter the one-way cable run length, not the round trip.
  3. Pick the maximum voltage drop, the routing environment and the conductor metal.
  4. Read the recommended wire size, the fuse suggestion, the actual voltage drop and the heat loss.

Worked example

A 300 W load at 12 V draws 25 A. Over a 4 m one-way run with a 3% drop limit (0.36 V), the formula 0.0175 × 2 × 4 × 25 / 0.36 gives 9.7 mm², so the tool picks the next standard size, 10 mm² (≈ 6 AWG, because 8 AWG is only 8.4 mm²). The real drop is 0.35 V (2.92%), using 97% of the allowance, with about 8.8 W lost as heat and a 40 A fuse suggested. The same 300 W at 24 V draws 12.5 A and needs only 2.5 mm² for the voltage drop alone, but the 20 A fuse it requires moves the tool's pick up to 4 mm² (≈ 12 AWG). This is a planning aid based on a simplified ampacity table, so confirm the final installation against the applicable code or a qualified electrician.

Why this tool exists and where its numbers come from

On 12 V and 24 V systems a small voltage drop is a large share of the supply, so cable size depends on current, length and the drop you accept. The tool uses Ohm's law with the resistivity of annealed copper; the fuse and ampacity values are its own planning assumptions, so follow the standard for your installation.

Sources

For the full method, see the Methodology section just below.

Methodology

Unlike high-voltage AC house wiring where ampacity alone often dictates the choice, 12 V and 24 V DC systems are overwhelmingly governed by voltage drop. Low voltage means high current for equivalent wattage (a 300 W load draws 25 A at 12 V but only 12.5 A at 24 V), causing severe voltage drops across long conductor lengths. The tool then checks the chosen size against a simplified thermal limit and the fuse rating.

Ohm's Law & Conductor Cross-Section: Cross-sectional conductor area is determined using S = (2 · ρ · L · I) / ΔV, where ρ is the resistivity of annealed copper (0.0175 Ω·mm²/m, slightly above the 0.01724 of the IEC annealed copper standard), L is the one-way distance in meters, I is operating current in Amps, and ΔV is maximum allowable voltage loss. Worked example: 300 W at 12 V is 25 A; over 4 m with a 3% limit (0.36 V) S = 0.0175 × 8 × 25 / 0.36 = 9.7 mm², so the next standard size, 10 mm² (≈ 6 AWG, because 8 AWG is only 8.4 mm²), is chosen, giving a real drop of 0.35 V (2.9%) and about 8.8 W of heat. The same 300 W at 24 V needs only 2.5 mm² for the voltage drop alone, but the 20 A fuse it requires moves the tool's pick up to 4 mm² (≈ 12 AWG). AWG and mm² sizes do not match exactly (8 AWG is 8.4 mm², smaller than 10 mm²), so the AWG shown next to a metric size is approximate; in AWG mode the tool selects by the real AWG area and may pick a larger cable than that approximation. Tinned copper uses a slightly higher resistivity; copper-clad aluminum is modeled with the resistivity of pure aluminum (0.0282), a deliberately pessimistic choice because CCA has higher DC resistance than copper of the same size.
Thermal Derating & Fuse Protection: The tool uses a simplified ampacity table for each cable size and multiplies it by 0.8 for enclosed conduit or wall bundles, and by 0.58 (a 42% reduction) for hot engine bays up to 60°C. These factors are conservative assumptions of this calculator, not values copied from a standard; real ratings depend on insulation temperature class, bundling and cable type. The recommended fuse is 125% of the operating current, rounded up to a standard size, and the cable is chosen so that its derated ampacity also covers that fuse. A fuse larger than the wire's rating leaves the wire unprotected. For reference, West Marine's marine wire guide lists ampacities for wire with 105°C insulation and says wire with lower-rated insulation must be derated.

Cable sizes from 100 W to 1 kW, and one fridge case

Tool defaults: 3% drop limit, enclosed conduit, copper, 3 m one-way run.

LoadCurrentCableFuseReal dropHeat
12 V · 100 W8.3 A2.5 mm² (≈ 14 AWG)15 A2.92%2.9 W
12 V · 300 W25 A10 mm² (≈ 6 AWG)40 A2.19%6.6 W
12 V · 600 W50 A35 mm² (≈ 2 AWG)80 A1.25%7.5 W
12 V · 1000 W83.3 A70 mm² (≈ 2/0 AWG)125 A1.04%10.4 W
24 V · 1000 W41.7 A25 mm² (≈ 4 AWG)60 A0.73%7.3 W
48 V · 1000 W20.8 A10 mm² (≈ 6 AWG)30 A0.46%4.6 W

Look at the 600 W row: the drop alone would allow 16 mm², but the 80 A fuse needs a cable whose derated ampacity covers it, so the tool moves up to 35 mm². Higher voltage shrinks everything: the same 1000 W needs 70 mm² at 12 V and 10 mm² at 48 V.

A fridge in a van. Lucía runs a 60 W compressor fridge (5 A) over 6 m one-way. At a 10% limit the tool accepts 1.5 mm² (≈ 16 AWG), but the real drop is 5.83% (0.70 V) with 3.5 W of heat. At 3% it asks for 4 mm² (≈ 12 AWG): 2.19% (0.26 V), 1.3 W. She chooses 4 mm², since a battery that sags under load leaves less margin before the fridge cuts out. The tool uses the steady current you enter, so use the higher figure if the load surges at start-up. Planning aid only, not electrical advice: have the final design checked against the applicable code or by a qualified electrician.

Essential Vanlife Electrical Hardware

A portable power station, a wire stripper and crimper, and a bus bar for 12 V installations

Portable LiFePO4 Power Power Station
Jackery Explorer 300 Portable Power Station (292 Wh)

Jackery Explorer 300 Portable Power Station (292 Wh)

A 292 Wh portable power station, according to the listing, for camping and backup power. Check its output limits against the load you plan to run.

Wiring & Crimping Tool Hand Tool
WGGE WG-015 Multi-Function Wire Stripper & Crimper (8-Inch)

WGGE WG-015 Multi-Function Wire Stripper & Crimper (8-Inch)

An 8-inch stripper, cutter and crimper for 10 to 22 AWG wire, according to the listing.

Heavy Duty Distribution Bus Bar Block
12 V 150 A Marine Bus Bar Power Distribution Block (1/4" Stud)

12 V 150 A Marine Bus Bar Power Distribution Block (1/4" Stud)

A 12 V bus bar rated at 150 A with 1/4-inch studs, according to the listing, for joining several cables at one point. Fuse each circuit as the calculator suggests.

As an Amazon Associate we earn from qualifying purchases at no additional cost to you.

Related tools

Frequently asked questions

Why is voltage drop much more dangerous in 12 V DC than 120 V/230 V AC? ▼

A 1.2 V drop on a 120 V household line is an insignificant 1% reduction. However, on a 12 V battery system, a 1.2 V drop represents a massive 10% loss. This triggers low-voltage disconnects on 12 V refrigerators, causes LiFePO4 battery monitoring errors, and produces dangerous heat in undersized wires.

What is the difference between one-way distance and total circuit loop length? ▼

Direct current requires electricity to flow from the battery positive terminal to the load and return via the negative cable to the battery. A physical run of 4 meters requires 8 meters of total wire. This calculator takes your one-way distance and automatically multiplies by 2 to compute the true electrical loop.

Should I use 3% or 10% allowable voltage drop for van conversions? ▼

The American Boat and Yacht Council (ABYC E-11, for boats) sets a maximum of 3% for critical circuits such as main feeders, bilge blowers, electronics and navigation lights, and 10% for non-critical circuits such as general lighting. There is no single mandatory rule for vans, so many builders borrow those marine limits. Use 1% to 3% for inverters, DC-DC chargers, solar controllers and compressor fridges, and treat 5% to 10% as acceptable only for LED lights or small fans.

Why does the tool recommend a bigger cable than the voltage drop alone requires? ▼

Because the fuse has to protect the cable, not just the appliance. The recommended fuse is 125% of the load current, rounded up, and the cable's derated ampacity must be at least that size. For a 25 A load the fuse is 40 A, so a cable rated only 27 A would be skipped even if its voltage drop is fine. Never install a fuse above the rating of the wire it protects.

Can I use copper-clad aluminum (CCA) cable? ▼

You can, but it needs a larger cross-section for the same drop. CCA has higher DC resistance than copper, and this calculator assumes pure-aluminum resistivity for it, which is why the result above jumps from 10 mm² to 16 mm². CCA also solders and crimps less reliably, so many installers use pure or tinned copper in vehicles and boats.